Smart Transmitter / Gas Detector
sd-1 series
SD-1, SD-1D
Features
・ATEX / IECEx certificate
・Flameproof enclosure for Acetylene and Hydrogen
・Self diagnosis by microprocesso
Model list
SD-1 (Diffusion type)
SD-1D (Suction type)
▶DTM software Download
Sampling method |
Suction type/Single type, Diffusion type/Single type |
Principle of detection |
Catalytic Combustion Method, New Ceramic catalytic Method |
Detection range |
TYPE GP : 0 to 100%LEL |
Alarm setpoints |
TYPE GP : 25%LEL |
Type of alarm |
Gas alarm / fault alarm |
Display of alarm |
Lamp lighting / information displayed |
Explosion protected construction |
Flameproof enclosures |
Explosion-proof class |
IECEx : Ex db ⅡC T5 Gb |
Ingress proof rating |
IP65 |
Approvals |
Japan Ex, ATEX, IECEx, Taiwan Ex, China Ex, MED |
CE marking |
EMC / ATEX / RoHS |
Power source |
24 VDC±10 % |
Dimensions |
Approx. 148(W) × 161(H) × 88(D) mm [SD-1] |
Weight |
Approx. 2.0 kg [SD-1] |
Operating temperature range |
-20 to +60℃ (no sudden changes) |
Operating humidity range |
0 to 95 %RH (no condensation) |